All about civil construction knowledge- PARAM VISIONS

Basic rules for lapping in column reinforcement. / 7 basic rules for providing Lap splice in column.

 Now, let us go through 7 basic rules while lapping the rebars in columns.

1. Lap length diameter:


When we extend the top bar of the column from the bottom bar, having an unequal diameter, then the lap length is calculated for the smaller dia. bar.

For eg., if the upper bar of 16mm dia. is lapped with a lower bar of 20mm dia., and if the lap length is taken as 50d, then

Lap length 50d = 50 × 16mm = 800mm. 👈correct

Lap length 50d = 50 × 20mm = 1000mm 👈 incorrect


2. Lapping zone :


When we provide lapping in a column, all the rebars should be lapped in zone B as shown in the drawing. The top and bottom portion of the column, i.e. zone-A ( L/4 length ) should be avoided as there will be a maximum moment in this zone due to lateral forces acting on the column. 

If the length of the column is L, then the L/4  length from the top & bottom of the column is categorized as tension zone A and the center L/2 length of the column (zone B ) is considered a safe area for the lapping purpose.

3. Staggered bar :




All the bars that are lapped should be staggered within zone B as shown in the above drawing. In any case, not more than 50% of rebars should be lapped at the same level. If all the column bars are lapped at the same level, it leads to the failure of the column.

4. Stirrup spacing :



The spacing of the stirrups in the lapping zone should be minimum when compared to the regular column c/c stirrup spacing.

If the designed regular spacing for the column stirrup is 175 c/c, then the spacing of stirrups in the lapping zone may be 150 c/c or 125 c/c, according to the column design.

5. Welding the rebar :



As per IS code, if the bar diameter is greater than or equal to 36mm, then you should consider welding those bars instead of lapping.  If welding is not possible, then you can lap these bars with an additional spiral of 6mm bar at the splice length.

6. Joggle length :


For the rebars of a diameter greater than 12mm, you can consider providing a joggle of 1 in 6. That means if the bar dia. is 20mm then the length of the joggled part of the bar can be calculated as 

J = 6 ×Diameter of rebar
  
    = 6 × 20mm = 120mm.

7.  Rebar placing:




When we tye the rebars in the lapping zone, the joggled part of the bar should be placed over the inner surface of the bottom bar (as shown in the above drawing ) to get a uniform clear cover from the concrete surface. 
If you tye the joggled portion of the rebar over the outer surface of the bottom bar, then the lapping zone invades the concrete cover area, provided for the bars.

Go through the articles 👇

1. Why top bar should be joggled during lapping in columns?/ Correct lapping procedure in column bars.

2. What is the difference between joggled bar & a staggered bar in civil construction?

3. Basic rules for providing lap splice in a beam reinforcement.


👀  To go through all types of construction-related procedures & checklistsclick here.

Thank you for going through this article. Have a good day 😄.

Share:

5 comments:

  1. You’ve provided great information in your blog. Many thanks for sharing the information in your blog. Black Optical Coating by Valley Design.

    ReplyDelete
  2. Thanks for the blog loaded with so many information. Stopping by your blog helped me to get what I was looking for. Wind Tunnel Polishing Services.

    ReplyDelete
  3. You’re an excellent blogger. I’m very impressed by your work and will recommend your tips to everyone in my circle so that they can also benefit from this information. Used Lapping Equipment for Sale.

    ReplyDelete
  4. I’d like to thank you for writing on this topic. The information you provided was very useful. I will visit again in the near future. Glass Lapping and Polishing Services for All Materials.

    ReplyDelete

Translate

Blog Archive

popular posts

Recent Posts

Google search